exceed 10 kVA in a section of the building classified as combustible or 75 kVA where the surrounding structure is classified as fire-resistant construction.
Exception No. 3: Electric furnace transformers that have a total rating not exceeding 75 kVA shall be permitted to be installed without a vault in a building or room of fire- resistant construction, provided suitable arrangements are made to prevent a transformer oil fire from spreading to other combustible material.
Exception No. 4: A transformer that has a total rating not exceeding 75 kVA and a supply voltage of 600 volts or less that is an integral part of charged-particle- accelerating equipment shall be permitted to be installed without a vault in a building or room of noncombustible or fire-resistant construction, provided suitable arrangements are made to prevent a transformer oil fire from spreading to other combustible material.
Exception No. 5: Transformers shall be permitted to be installed in a detached building that does not comply with Part 111 of this article if neither the building nor its contents present afire hazard to any other building or property, and if the building is used only in supplying electric service and the interior is accessible only to qualified persons. Exception No. 6: Oil-insulated transformers shall be permitted to be used without a vault in portable and mobile surface mining equipment (such as electric excavators) if each of the following conditions is met:
(a) Provision is made for draining leaking fluid to
the ground.
(b) Safe egress is provided for personnel.
(c) A minimum 6-mm ('A-in.) steel barrier is
provided for personnel protection.
450.27 Oil-Insulated Transformers Installed Outdoors.
Combustible material, combustible buildings, and parts of buildings, fire escapes, and door and window openings shall be safeguarded from fires originating in oil-insulated transformers installed on roofs, attached to or adjacent to a building or combustible material.
In cases where the transformer installation presents a fire hazard, one or more of the following safeguards shall be applied according to the degree of hazard involved:
(1) Space separations
(2) Fire-resistant barriers
(3) Automatic fire suppression systems
(4) Enclosures that confine the oil of a ruptured trans- former tank
Oil enclosures shall be permitted to consist of fire- resistant dikes, curbed areas or basins, or trenches filled with coarse, crushed stone. Oil enclosures shall be provided with trapped drains where the exposure and the quantity of oil involved are such that removal of oil is important.
FPN: For additional information on transformers installed on poles or structures or under ground, see ANSI C2-2007, National Electrical Safety Code.