402-Fixture Wires

You are here

402.1 Scope. This article covers general requirements and construction specifications for fixture wires.

402.2 Other Articles. Fixture wires shall comply with this article and also with the applicable provisions of other articles of this Code.

FPN: For application in luminaires, see Article 410.

Table 402.3 Fixture Wires

402.3 Types. Fixture wires shall be of a type listed in Table 402.3, and they shall comply with all equirements of that table. The fixture wires listed in Table 402.3 are all suitable for service at 600 volts, nominal, unless therwise specified.

FPN: Thermoplastic insulation may stiffen at temperatures colder than -10°C (+14°F), requiring that care be exercised during installation at such temperatures. Thermoplastic insulation may also be deformed at normal temperatures where subjected to pressure, requiring that care be exercised during installation and at points of support.

Name

Type

Letter

Insulation

Thickness of Insulation

Outer

Covering

Maximum

Operating

Temperature

Application

Provisions

Name

Type

Letter

Insulation

AWG mm

mils

Outer

Covering

Maximum

Operating

Temperature

Application

Provisions

Heat-resistant

rubber- covered

fixture wire —

flexible

FFH-2

Heat-resistant

rubber

Cross-linked synthetic

polymer

18-16 0.76

18-16 0.76

30

30

Nonmetallic covering

75°C

167°F

Fixture wiring

ECTFE —

solid or 7- strand

HF

Ethylene

chlorotri- fluoroethylene

18-14 0.38

15

None

150°C

302°F

Fixture wiring

ECTFE —

flexible stranding

HFF

Ethylene

chlorotriflu- oroethylene

18-14 0.38

15

None

150°C

302°F

Fixture wiring

Tape insulated

fixture wire

— solid or

7-strand

KF-1

KF-2

Aromatic

polyimide tape Aromatic polyimide tape

18-10 0.14

18-10 0.21

5.5

8.4

None

None

200°C

392°F

200°C

392°F

Fixture wiring

— limited to

300 volts

Fixture wiring

Tape insulated

fixture wire

— flexible stranding

KFF-1

KFF-2

Aromatic

polyimide tape Aromatic polyimide tape

18-10 0.14

18-10 0.21

5.5

8.4

None

None

200°C

392°F

200°C

392°F

Fixture wiring

— limited to

300 volts

Fixture wiring

(Continues)

Table 4023 Continued

Name

Type

Letter

Insulation

Thickness of Insulation

Outer

Covering

Maximum

Operating

Temperature

Application

Provisions

Name

Type

Letter

Insulation

AWG mm

mils

Outer

Covering

Maximum

Operating

Temperature

Application

Provisions

Perfluoro- alkoxy — solid or 7-strand (nickel or nickel-coated copper)

PAF

Perfluoro- alkoxy

18-14 0.51

20

None

250°C

482°F

Fixture wiring (nickel or nickel-coated copper)

Perfluoro-alkoxy

— flexible

stranding

PAFF

Perfluoro- alkoxy

18-14 0.51

20

None

150°C

302°F

Fixture wiring

Fluorinated ethylene propylene fixture wire — solid or 7- strand

PF

Fluorinated

ethylene propylene

18-14 0.51

20

None

200°C

392°F

Fixture wiring

Fluorinated ethylene propylene fixture wire — flexible stranding

PFF

Fluorinated

ethylene propylene

18-14 0.51

20

None

150°C

302°F

Fixture wiring

Fluorinated ethylene propylene fixture wire — solid or 7- strand

PGF

Fluorinated

ethylene propylene

18-14 0.36

14

Glass braid

200°C

392°F

Fixture wiring

Fluorinated ethylene propylene fixture wire — flexible stranding

PGFF

Fluorinated

ethylene propylene

18-14 0.36

14

Glass braid

150°C

302°F

Fixture wiring

Extruded polytetraflu- oroethylene — solid or 7- strand (nickel

or nickel-coated copper)

PTF

Extruded polytetraflu- oroethylene

18-14 0.51

20

None

250°C

482°F

Fixture wiring (nickel or nickel-coated copper)

Table 402.3 Continued

Name

Type

Letter

Insulation

Thickness of Insulation

Outer

Covering

Maximum

Operating

Temperature

Application

Provisions

Name

Type

Letter

Insulation

AWG mm

mils

Outer

Covering

Maximum

Operating

Temperature

Application

Provisions