402-Fixture Wires: Page 3 of 3

You are here

connecting luminaires to the branch-circuit conductors supplying the luminaires.
402.11 Uses Not Permitted. Fixture wires shall not be used as branch-circuit conductors except as permitted elsewhere in the Code.

402.12 Overcurrent Protection. Overcurrent protection for fixture wires shall be as specified in 240.5.

Size (AWG)

18

Allowable Ampacity

6

16

8

14

17

12

23

10

28

402.6 Minimum Size. Fixture wires shall not be smaller than 18 AWG.

402.7 Number of Conductors in Conduit or Tubing. The number of fixture wires permitted in a single conduit or tubing shall not exceed the percentage fill specified in Table 1, Chapter 9.

402.8 Grounded Conductor Identification. Fixture wires that are intended to be used as grounded conductors shall be identified by one or more continuous white stripes on other than green insulation or by the means described in 400.22(A) through (E).

402.9 Marking.

(A) Method of Marking. Thermoplastic insulated fixture wire shall be durably marked on the surface at intervals not exceeding 610 mm (24 in.). All other fixture wire shall be marked by means of a printed tag attached to the coil, reel, or carton.

(B) Optional Marking. Fixture wire types listed in Table

402.3 shall be permitted to be surface marked to
indicate special characteristics of the cable materials.
These markings include, but are not limited to,
markings for limited smoke, sunlight resistance, and so
forth.
402.10 Uses Permitted. Fixture wires shall be permitted (1) for installation in luminaires and in similar equipment where enclosed or protected and not subject to bending or twisting in use, or (2) for