shall be provided with a clearly identified and readily accessible switch or other acceptable means, located remote from the
dispensing devices, to disconnect simultaneously from the source of supply, all conductors of the circuits,including the grounded conductor, if any.
Single-pole breakers utilizing handle ties shall not be permitted.
(B) Attended Self-Service Motor Fuel Dispensing Fa- cilities. Emergency controls as specified in 514.11(A) shall be installed at a location acceptable to the authority having jurisdiction, but controls shall not be more than 30 m (100 ft) from dispensers. [30A:6.7.1]
(C) Unattended Self-Service Motor Fuel Dispensing
Facilities. Emergency controls as specified in
514.11(A) shall be installed at a location acceptable to
the authority having jurisdiction, but the control shall
be more than 6 m (20 ft) but less than 30 m (100 ft)
from the dispensers. Additional emergency controls
shall be installed on each group of dispensers or the
outdoor equipment used to control the dispensers.
Emergency controls shall shut off all power to all
dispensing equipment at the station. Controls shall be
manually reset only in a manner approved by the
authority having jurisdiction. [30A:6.7.2]
FPN: For additional information, see 6.7.1 and 6.7.2 of NFPA 30A-2008, Code for Motor Fuel Dispensing Facilities and Repair Garages.