any one ungrounded conductor plus the inverter output rating shall not exceed the ampacity of the neutral conductor.
705.100 Unbalanced Interconnections.
(A) Single Phase. Single-phase inverters for hybrid sys- tems and ac modules in interactive hybrid systems shall not be connected to 3-phase power systems unless the interconnected system is designed so that significant unbalanced voltages cannot result.
(B) Three Phase. Three-phase inverters and 3-phase ac modules in interactive systems shall have all phases automatically de-energized upon loss of, or unbalanced, voltage in one or more phases unless the interconnected system is designed so that significant unbalanced
voltages will not result.