(I) Cable Marking. The cable shall be marked in accor- dance with Table 760.179(1). The voltage rating shall not be marked on the cable. Cables that are listed for circuit integrity shall be identified with the suffix CI as defined in 760.179(G).

FPLP Power-limited fire alarm
plenum cable
FPLR Power-limited fire alarm riser cable
FPL Power-limited fire alarm cable
Note: Cables identified in 760.179(D), (E), and (F) as meeting the requirements for circuit integrity shall have the additional classification using the suffix "CI" (for example. FPLP-CI, FPLR-CI, and FPL-CI).
FPN: Cable types are listed in descending order of fire- resistance rating.

(J) Insulated Continuous Line-Type Fire Detectors. In- sulated continuous line-type fire detectors shall be rated in accordance with 760.179(C), listed as being resistant to the spread of fire in accordance with

760.179(D) through (F), marked in accordance with
760.179(1), and the jacket compound shall have a high
degree of abrasion resistance.