625-Electric Vehicle Charging System: Page 5 of 5

You are here

vehicle supply equipment and shall remain

Table 625.29(D)(1) Minimum Ventilation Required in Cubic Meters per Minute (m 3/min) for Each of the Total Number of
Electric Vehicles That Can Be Charged at One Time

Branch-Circuit Voltage

(5)

Branch- Single Phase 3 Phase

Circuit

Ampere 240 V or 208 V or 480 V or 600 V or

Rating 120 V 208 V 120/240 V 208Y/120 V 240 V 480Y/277 V 600Y/347 V

15 1.1 1.8 2.1

20 1.4 2.4 2.8 4.2 4.8 9.7 12

30 2.1 3.6 4.2 6.3 7.2 15 18

40 2.8 4.8 5.6 8.4 9.7 19 24

50 3.5 6.1 7.0 10 12 24 30

60 4.2 7.3 8.4 13 15 29 36

100 7.0 12 14 21 24 48 60

150 — — — 31 36 73 91

200 — — — 42 48 97 120

250 — — — 52 60 120 150

300 — — — 63 73 145 180

350 — — — 73 85 170 210

400 — — 84 97 195 240

Table 625.29(D)(2) Minimum Ventilation Required in Cubic Feet per Minute (cfm) for

Each of the Total Number of Electric Vehicles That Can Be Charged at One Time

Branch-Circuit Voltage

Single Phase 3 Phase

Branch-Circuit

Ampere

240 V or 208 V or 480 V or 600 V or

Rating 120 V 208 V 120/240 V 208Y/120 V 240 V 480Y/277 V 600Y/347 V

15 37 64 74

20 49 85 99 148 171 342 427

30 74 128 148 222 256 512 641

40 99 171 197 296 342 683 854

50 123 214 246 370 427 854 1066

60 148 256 296 444 512 1025 1281

100 246 427 493 740 854 1708 2135

150 — — — 1110 1281 2562 3203

200 — — — 1480 1708 3416 4270

250 — — — 1850 2135 4270 5338

300 — — — 2221 2562 5125 6406

350 — — — 2591 2989 5979 7473

400 — — — 2961 3416 6832 8541

energized during the entire electric vehicle charging cycle. Electric vehicle supply equipment shall be marked in accordance with 625.15. Electric vehicle supply equipment receptacles rated at 125 volts, single phase, 15 and 20 amperes shall be marked in accordance with
625.15(C) and shall be switched, and the mechanical ventilation system shall be electrically interlocked through the switch supply power to the receptacle.

625.30 Outdoor Sites. Outdoor sites shall include but not be limited to residential carports and driveways, curbside, open parking structures, parking lots, and commercial charging facilities.

(A) Location. The electric vehicle supply equipment shall be located to permit direct connection to the electric

vehicle.

(B) Height Unless specifically listed for the purpose and location, the coupling means of electric vehicle supply equipment shall be stored or located at a height of not less than 600 mm (24 in.) and not more than 1.2 m (4 ft) above the parking surface.