FPLR 760.154(B) CMP, FPLP, CMR FPL 760.154(C) CMP, FPLP, CMR, FPLR, CMG, CM
(A) NPLFA Conductor Materials. Conductors shall be 18
AWG or larger solid or stranded copper.
(B) Insulated Conductors. Insulated conductors shall be suitable for 600 volts. Insulated conductors 14 AWG and larger shall be one of the types listed in Table 310.13(A) or one that is identified for this use. Insulated conductors 18 AWG and 16 AWG shall be in accordance with 760.49.
(C) Type NPLFP. Type NPLFP non-power-limited fire alarm cable for use in other space used for environmental air shall be listed as being suitable for use in other space used for environmental air as described in 300.22(C) and shall also be listed as having adequate fire-resistant and low smoke-producing characteristics.
FPN: One method of defining low smoke-producing cable is by establishing an acceptable value of the smoke produced when tested in accordance with NFPA
262-2007, Standard Method of Test for Flame Travel
and Smoke of Wires and Cables for Use in Air-Handling
Spaces, to a maximum peak optical density of 0.5 and a
maximum average optical density of 0.15. Similarly, one method of defining fire-resistant cables is by establishing a maximum allowable flame travel distance of 1.52 m (5 ft) when tested in accordance with the
same test.
(D) Type NPLFR. Type NPLFR non-power-limited fire alarm riser cable shall be listed as being suitable for use in a vertical run in a shaft or from floor to floor and shall also be listed as having fire-resistant characteristics capable of preventing the carrying of fire from floor to floor.
FPN: One method of defining fire-resistant characteristics capable of preventing the carrying of
1666-2002, Test for Flame Propagation Height of
General purpose CM
FPL
Electrical and Optical-Fiber Cables Installed Vertically in Shafts.
Type CM—Communications wires and cables Type
FPL—Power-limited fire alarm cables
(E) Type NPLF. Type NPLF non-power-limited fire alarm cable shall be listed as being suitable for general- purpose
fire alarm use, with the exception of risers, ducts, plenums, and other space used for environmental air, and shall also be listed as being resistant to the spread of fire.
FPN: One method of defining resistant to the spread of fire is that the cables do not spread fire to the top of the tray in the "UL Flame Exposure, Vertical Tray Flame Test" in UL 1685-2000, Standard for Safety for Vertical- Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables. The smoke measurements in the test method are not applicable.
Another method of defining resistant to the spread of fire is for the damage (char length) not to exceed 1.5 m (4 ft 11 in.) when performing the CSA "Vertical Flame Test — Cables in Cable Trays," as described in CSA C22.2 No. 0.3-M-2001, Test Methods for Electrical Wires and Cables.
(F) Fire Alarm Circuit Integrity (CI) Cable or Electri
cal Circuit Protective System. Cables used for survivabil
ity of critical circuits shall be listed as circuit integrity
(CI) cable. Cables specified in 760.176(C), (D), and (E),
and used for circuit integrity shall have the additional