392-Cable Trays: Page 6 of 10

You are here

Rated 2000 Volts or Less

Inside Width of

Cable Tray

Maximum Allowable Fill Area for Multiconductor Cables

Inside Width of

Cable Tray

Ladder or Ventilated Trough Cable Trays,

392.9(A)

Solid Bottom Cable Trays, 392.9(C)

Inside Width of

Cable Tray

Column 1

Applicable for

392.9(A)(2) Only

Column 2" Applicable for 392.9(A)(3) Only

Column 3

Applicable for

392.9(C)(2) Only

Column 4"

Applicable for 392.9(C)(3) Only

mm in.

mm2 in.2

mm2 in.2

mm2 in.2

mm2 in.2

150 6.0

225 9.0

300 12.0

450 18.0

600 24.0

750 30.0

900 36.0

4,500 7.0

6,800 10.5

9,000 14.0

13,500 21.0

18,000 28.0

22,500 35.0

27,000 42.0

4,500 - (30 Sd) b 7-(1.2Sd)b 6,800-

(30 Sd) 10.5-(1.2 Sd) 9,000-(30

Sd) 14-(1.2Sd) 13,500-(30 Sd)

21- (1.2 Sd) 18,000-(30 Sd) 28- (1.2Sd) 22,500 - (30 Sd) 35-

(1.2Sd) 27,000 - (30 Sd) 42- (1.2Sd)

3,500 5.5

5,100 8.0

7,100 11.0

10,600 16.5

14,200 22.0

17,700 27.5

21,300 33.0

3,500-(25 Sd b) 5.5-Sd b

5,10O-(25 Sd) 8.0-Sd

7,100-(25 Sd) 11.0-Sd

10,600-(25 Sd) 16.5-Sd

14,200-(25 Sd) 22.0-Sd

17,700-(25 Sd) 27.5-Sd

21,30O-(25 Sd) 33.0-Sd

aThe maximum allowable fill areas in Columns 2 and 4 shall be calculated. For example, the maximum allowable fill in mm 2 for a 150-mm wide cable tray in Column 2 shall be 4500 minus (30 multiplied by Sd) [the maximum allowable fill, in square inches, for a 6-in. wide cable tray in Column 2 shall be 7 minus (1.2 multiplied by Sd)].

'The term Sd in Columns 2 and 4 is equal to the sum of the diameters, in mm, of all cables 107.2 mm (in inches, of all 4/0 AWG) and larger multiconductor cables in the same cable tray with smaller cables.

(D) Solid Bottom Cable Tray — Multiconductor Con trol and/or Signal Cables Only. Where a solid bottom cable tray having a usable inside depth of 150 mm (6 in.) or less contains multiconductor control and/or signal cables only, the sum of the cross-sectional areas of all cables at any cross section shall not exceed 40 percent of the interior cross-sectional area of the cable tray. A depth of 150 mm (6 in.) shall be used to calculate the allowable interior cross-sectional area of any cable tray that has a usable inside depth of more than 150 mm (6 in.).

(E) Ventilated Channel Cable Trays. Where ventilated channel cable trays contain multiconductor cables of any type, the following shall apply:

(1) Where only one multiconductor cable is installed, the cross-sectional area shall not exceed the value specified in Column 1 of Table 392.9(E).

(2) Where more than one multiconductor cable is installed, the sum of the cross-sectional area of all cables shall not exceed the value specified in Column 2 of Table 392.9(E).

(F) Solid Channel Cable Trays. Where solid channel cable trays contain multiconductor cables of any type, the following shall apply:

(1) Where only one multiconductor cable is installed, the cross-sectional area of the cable shall not exceed the value specified in Column 1 of Table

392.9(F).

(2) Where more than one multiconductor